Interface Modules
8-11
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
8.3 IM151-1 STANDARD interface module
(6ES7 151-1AA04 -0AB0)
Order number
6ES7 151-1AA04-0AB0
Properties
The IM151-1 STANDARD interface module has the following features:
It connects the ET 200S with PROFIBUS DP via the RS485 interface.
It prepares the data for the electronic modules and motor starters that are fitted.
It supplies the backplane bus.
The PROFIBUS DP address of the ET 200S can be set by means of switches.
If the 24 VDC power supply is disconnected, the IM151-1 STANDARD interface
module is also disconnected.
The maximum address space is 244 bytes for inputs, and 244 bytes for outputs.
The reference potential M of the rated supply voltage of the
IM151-1 STANDARD to the rail (protective conductor) is connected by means
of an RC combination, thus permitting an ungrounded configuration.
Operation as a DPV0 slave.
A maximum of 63 modules can be operated with the IM151-1 ST ANDARD.
The maximum bus length is 2 m (can be set).
Supports option handling (see Chapter 3.8) and the status byte for power
modules.
Supplementary properties compared to the IM151-1 STANDARD interface module
(up to 6ES7 151-1AA03-0AB0):
Operation as a DPV1 slave.
-- Acyclic data exchange (read/write data record):
class 2 services and class 1 services
-- Diagnostics Interrupts
-- Process Alarms
-- Removal/Insertion Interrupt
Firmware update via PROFIBUS DP
Identification data (see Sec. 3.9)