Commissioning and Diagnostics
6-56
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
6.1.6.10 Diagnostics in the case of in valid ET 200S configuration states
on the PROFIBUS DP
Invalid configuration states
The following invalid configuration states of the ET 200S lead to station failure of
the ET 200S or prevent entry into data interchange. These responses occur
irrespective of whether the IM parameters ”Operation at Preset <> Actual
Configuration”, Replacement of Modules during Operation”, and ”Startup when
Expected <> Actual Configuration” have been enabled.
T wo missing modules
Bus termination module missing
Number of modules exceeds maximum configuration
Module missing in slot 1 (in the case of the IM151-1 STANDARD,
6ES7 151-1AA00-0AB0)
Faulty backplane bus (for example, terminal module is defective)
Note
As of IM151-1 BASIC / IM151-1 STANDARD (6ES7 151-1AA01-0AB0), IM151-1
FO STANDARD and IM151-1 HIGH FEATURE: If one module is missing (gap) and
the ET 200S is switched on, the station will not start up (see diagnosis below).
Diagnostics
The following diagnosis indicates all the invalid configuration states:
Interface module ID -related diagnostics Module status
IM151-1 BASIC All 12 bits set
01
B
: ”Module error; invalid user data” for
a
m
o
d
u
e
s
(
s
o
t
s
)
u
n
t
t
h
e
c
a
u
s
e
o
f
t
h
e
IM151-1 STANDARD
IM151-1 FO STANDARD
IM151-1 HIGH FEATURE
All 63 bits set
a
m
o
d
u
e
s
(
s
o
t
s
)
u
n
t
t
h
e
c
a
u
s
e
o
f
t
h
e
error is found
11
B
: ”No module; invalid user data” once
the cause of the error is found