General Technical Specifications
7-11
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Rated voltage for operation
The ET 200S distributed I/O system works with the rated voltage and
corresponding tolerances specified in the following table.
ET 200S modules Rated voltage Tolerance range
Everything except
24 VDC 20.4 to 28.8 VDC
1)
motor starters
18.5 to 30.2 VDC
2)
120 VAC VAC to 132 VAC (47 Hz to 63 Hz)
230 VAC VAC to 264 VAC (47 Hz to 63 Hz)
1)
static value: generation as functional extra-low voltage with safe electrical
isolation as per IEC 60364-4-41
2)
dynamic value: including ripple e. g. with three-phase bridge rectification
7.5 Variations in technical data for the
ET 200S FC frequency converter
The following table shows variations in the general technical data for the
ET 200S FC frequency converter compared to the ET 200S.
Table 7-2 Variations in technical data for the ET 200S FC frequency
converter
Chapter
different values
Standards, certificates and approvals The frequency converter is not approved
under
•
cULus for HAZ.LOC.
•
FM (Factory Mutual Research)
•
shipbuilding
Shipping and storage conditions Free fall: ≤ 0.35 m
Climatic ambient conditions Temperature for horizontal installation:
from0to60°C
Temperature for vertical installation:
from0to40°C
Mechanical ambient conditions See operating manual for ET 200S FC
Rated operational voltage
requency conver
er
(6SL3 298-0CA12-0xP0)
UseinZone2 The ET 200S FC frequency converter is not
approved for operation in Zone 2 hazardous
atmosphere.