Configuration Options
3-7
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
3.4 Configuration options of the interface modules
The interface module to suit your application:
Table 3-3 Interface modules and the applications for which they are suited
Applications
Interface module
•
Connecting the PROFIBUS DP by means of the
RS 485 interface
•
Operation as a DPV0 slave.
•
Direct Data Exchange
•
Bus length of the ET 200S: irrelevant
•
Number of modules: max. 12
Transmission rates:
9.6; 19.2; 45.45; 93.75;
187.5; 500 kbps,
1.5 ; 3; 6; 12 Mbps
IM151-1 BASIC
•
Connecting the PROFIBUS DP by means of the
RS 485 interface
•
Operation as a DPV0 slave.
•
Direct Data Exchange
•
Bus length of the ET 200S: max. 2 m
(configurable)
•
Number of modules: max. 63
•
Option handling and status byte for
power modules
from 6ES7 151-1AA04-0AB0 additionally:
•
Operation as a DPV1 slave.
-- Acyclic data exchange (read/write data record):
-- Diagnostics Interrupts
-- Process Alarms
-- Removal/Insertion Interrupt
•
Firmware update via PROFIBUS DP
•
Identification data
Transmission rates:
9.6; 19.2; 45.45; 93.75;
187.5; 500 kbps,
1.5 ; 3; 6; 12 Mbps
IM151-1 STANDARD
•
Connecting the PROFIBUS DP by means of
fiber-optic cable
•
Operation as a DPV0 slave.
•
Direct Data Exchange
•
Bus length of the ET 200S: max. 2 m
(configurable)
•
Number of modules: max. 63
•
Option handling and status byte for
power modules
from 6ES7 151-1AB03-0AB0 additionally:
•
Operation as a DPV1 slave.
-- Acyclic data exchange (read/write data record):
-- Diagnostics Interrupts
-- Process Alarms
-- Removal/Insertion Interrupt
•
Firmware update via PROFIBUS DP
•
Identification data
Transmission rates:
9.6; 19.2; 45.45; 93.75;
187.5; 500 kbps, 1.5 ;
12 Mbps
IM 151-1 FO
STANDARD