Analog Electronic Modules
12-32
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Parameters for
• 2AI RTD Standard analog electronic module
• 2AI TC Standard analog electronic module
• 2AI TC High Feature analog electronic module
Table 12-33 Parameters RTD, TC analog electronic modules
2AI RTD
Standard
2AI TC
Standard
2AI TC High
Feature
Value range Default
setting
Effective
range
Group diagnostics
(configuration error, internal error)
•
disable
•
enabled
disable Module
Diagnosis: underflow/overflow
•
disable
•
enabled
disable Module
Diagnosis:
wire break
2)
Diagnosis: wire-break test
1)
•
disable
•
enabled
disable Channel
Smoothing
•
No
•
weak
•
medium
•
strong
No Channel
Temperature
Unit
•
Centigrade
•
Fahrenheit
Centigrade Module
-- -- -- Reference
junction
-- -- --
•
No
•
RTD
No Channel
-- -- -- Reference
junction
•
No
•
Yes (means internal)
No Channel
-- -- -- Reference
junction
number
-- -- --
•
No
•
1to8
(with IM151-1
STANDARD, IM151-1
No Module
•
1
(with IM151-1 BASIC,
IM151-1 HIGH
FEATURE)
Measurement
type / range
-- -- --
•
disabled
•
150 ohms
•
300 ohms
•
600 ohms
•
Pt100 climate range
•
Ni100 climate range
•
Pt100 standard range
•
Ni100 standard range
Pt100
standard
range
Channel