EasyManua.ls Logo

Siemens SIMATIC ET 200S - Parameters for 2 AI RTD Standard analog electronic module

Siemens SIMATIC ET 200S
652 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Electronic Modules
12-32
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Parameters for
• 2AI RTD Standard analog electronic module
• 2AI TC Standard analog electronic module
• 2AI TC High Feature analog electronic module
Table 12-33 Parameters RTD, TC analog electronic modules
2AI RTD
Standard
2AI TC
Standard
2AI TC High
Feature
Value range Default
setting
Effective
range
Group diagnostics
(configuration error, internal error)
•
disable
•
enabled
disable Module
Diagnosis: underflow/overflow
•
disable
•
enabled
disable Module
Diagnosis:
wire break
2)
Diagnosis: wire-break test
1)
•
disable
•
enabled
disable Channel
Smoothing
•
No
•
weak
•
medium
•
strong
No Channel
Temperature
Unit
•
Centigrade
•
Fahrenheit
Centigrade Module
-- -- -- Reference
junction
-- -- --
•
No
•
RTD
No Channel
-- -- -- Reference
junction
•
No
•
Yes (means internal)
No Channel
-- -- -- Reference
junction
number
-- -- --
•
No
•
1to8
(with IM151-1
STANDARD, IM151-1
F
O
S
T
A
N
D
A
R
D
)
No Module
F
O
S
T
A
N
D
A
R
D
)
•
1
(with IM151-1 BASIC,
IM151-1 HIGH
FEATURE)
Measurement
type / range
-- -- --
•
disabled
•
150 ohms
•
300 ohms
•
600 ohms
•
Pt100 climate range
•
Ni100 climate range
•
Pt100 standard range
•
Ni100 standard range
Pt100
standard
range
Channel

Table of Contents