Digital Electronic Modules
11-3
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Parameters for 4DI NAMUR
Table 11-2 Parameters for 4DI NAMUR
Diagnostic alarm
•
enabled
•
disable
disable Module
Sensor type
•
Channel disabled
•
NAMUR sensor
•
Single c ontact
without load resistance
•
Single c ontact with 10 kΩ
with load resistance
•
NAMUR changeover
contact
•
Changeover contact
without load resistance
•
Changeover contact with
10 kΩ
with load resistance
disable Channel
Pulse stretching
•
No
•
0.5 s
•
1s
•
2s
No Channel
Diagnostics
No sensor power supply
•
enabled
•
disable
disable Module
Wire break diagnostics
•
enabled
•
disable
disable Channel
Short-circuit diagnostics
•
enabled
•
disable
disable Channel
Flutter monitoring:
Monitoring window
1)
•
0.5 s
•
1 s to 100s (can be set in
1 s increments)
0.5 s Channel
Flutter monitoring:
Number of signal changes
•
disable
•
2to31
disable Channel
1)
Parameters can only be set if the number of signal changes for flutter monitoring is enabled