Analog Electronic Modules
12-31
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Parameters for
2AI U High Speed analog electronic module
2AI I 2WIRE High Speed electronic module
2AI I 4WIRE High Speed electronic module
Table 12-32 Parameters for analog input modules U, I High Speed
2AI U High
Speed
2AII2WIRE
High Speed
2AII4WIRE
High Speed
Value range Default setting Effective range
Group diagnostics
(configuration error, internal error)
disable
enabled
disable Module
Diagnosis: underflow/overflow
disable
enabled
disable Module
-- -- -- Diagnosis:
Wire break
Diagnosis:
Wire break
disable
enabled
disable Channel
Smoothing
No
weak
medium
strong
No Channel
Measurement
type / range
-- -- -- -- -- --
disabled
10 V
5V
2.5 V
1to5V
10 V Channel
-- -- -- Measurement
type / range
-- -- --
disabled
4to20mA
0to20mA
4to20mA Channel
-- -- -- -- -- -- Measurement
type / range
disabled
4to20mA
0to20mA
20 mA
4to20mA Channel
Note
If you disable a channel of the High Speed modules, this will not increase speed
because of the measuring process in use.