Commissioning and Diagnostics
6-50
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Diagnostic interrupt, byte x+4 to x+7
Byte x+4
76 054321
Internal error in module
Module problem (i.e. error detected)
0000
Byte x+6
76 054321
Module class:
0100
B
for IM151-1 (STANDARD, HIGH FEATURE)
1001
B
for digital electronic module: as of byte x+8
0101
B
for analog electronic module: as of byte x+8
1000
B
for process-related module: as of byte x+8
1101
B
for power module: as of byte x+8
0
External error: Module not responding
Channel error in module
0
Channel information available (always ”1”)
User information available (always ”0”)
Byte x+5
70
Always ”0”
Byte x+7
70
Always ”0”
Incoming diagnosis: 1101
B
Going diagnosis: 0000
B
Figure 6-28 Structure of bytes x+4 to x+7 for diagnostic interrupt