EasyManua.ls Logo

Siemens SIMATIC ET 200S - Structure of Bytes X+4 to X+7 for Diagnostic Interrupt

Siemens SIMATIC ET 200S
652 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning and Diagnostics
6-50
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Diagnostic interrupt, byte x+4 to x+7
Byte x+4
76 054321
Internal error in module
Module problem (i.e. error detected)
0000
Byte x+6
76 054321
Module class:
0100
B
for IM151-1 (STANDARD, HIGH FEATURE)
1001
B
for digital electronic module: as of byte x+8
0101
B
for analog electronic module: as of byte x+8
1000
B
for process-related module: as of byte x+8
1101
B
for power module: as of byte x+8
0
External error: Module not responding
Channel error in module
0
Channel information available (always ”1”)
User information available (always ”0”)
Byte x+5
70
Always ”0”
Byte x+7
70
Always ”0”
Incoming diagnosis: 1101
B
Going diagnosis: 0000
B
Figure 6-28 Structure of bytes x+4 to x+7 for diagnostic interrupt

Table of Contents

Other manuals for Siemens SIMATIC ET 200S

Related product manuals