EasyManua.ls Logo

Siemens SIMATIC ET 200S - Page 165

Siemens SIMATIC ET 200S
652 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning and Diagnostics
6-5
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Note
if the modules are grouped in DPV1 operation in STEP 7 applications with
IM151-1 ST ANDARD, IM151-1 FO STANDARD or IM151-1 HIGH FEATURE,
No insert/remove-module interrupts (OB 83) are triggered for these modules. In
this case, you can recognize a module that has been removed from the module
status in the diagnostic frame in the cyclic user program.
Each grouped module then receives its own diagnostic address.
-- There can be a total of no more than 8 channels (1 byte).
3. Select from the hardware catalog of your configuration software the module
designation without *”. Result: you open a byte and store the first module
there.
4. Select from the hardware catalog of your configuration software the module
designation with *”. Result: in the open byte, you store additional modules until
all the bits are occupied.
5. If a byte is filled, you must configure a module again (that is, open a new byte
without *”).
Note
Configuration with the device database file: The configuration software does
not check whether the modules have been grouped correctly. If you configure
more than 8 channels in one byte, the modules that exceed the byte limit are
reported as being incorrectly configured in the diagnosis:
Module status 10
B
: wrong module; invalid user data
These modules are not addressed.

Table of Contents

Other manuals for Siemens SIMATIC ET 200S

Related product manuals