Digital Electronic Modules
11-22
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Technical data
Dimensions and weight
Dimensions W x H x D
(mm)
15 x 81 x 52
Weight Approx. 35 g
Module-specific data
Supports clock synchro-
nized mode
Yes
Number of inputs 2
Cable length
Unshielded max. 600 m (164 ft)
shielded max. 1,000 m (164
ft)
Voltages, currents, electrical potentials
Rated supply voltage (from
power module)
24 VDC
Polarity reversal
protection
Yes
Electrical isolation
Between the channels No
Between channels and
backplane bus
Yes
Permissible potential differ-
ence
Between different
circuits
75 VDC / 60 VAC
Insolation tested with 500 VDC
Current consumption
From power supply Dependent on the
sensor
Power loss of the module Typical 0.4 W
Status, interrupts, diagnostics
Status display Green LED per
channel
Interrupts
Process alarm Configurable
Diagnostic functions
Group error red LED ”SF”
Reading of diagnostic
data
Yes
Sensor power supply output
Output voltage
Loaded Min. L+ (--0.5 V)
Output current
Rated v alue 500 mA
Permitted range 0to500mA
Short-circuit protection Yes, electronic
1)
Data for selecting an sensor
Input voltage
Rated v alue
for ”1” signal
for ”0” signal
24 VDC
11 to 30 V
--30to5V
Input current
For signal ”1” Typical 8 mA
Input delay
(configurable)
”0” to ”1” transition 0.1 ms
(0.05to0.15ms)
0.5 ms
(0.4 to 0.6 ms)
3ms
(2.7 to 3.3 ms)
15 ms
(14.85 to 15.15 ms)
”1” to ”0” transition 0.1 ms
(0.05to0.15ms)
0.5 ms
(0.4 to 0.6 ms)
3ms
(2.7 to 3.3 ms)
15 ms
(14.85 to 15.15 ms)
Input characteristic curve To IEC 61131,
type 1
Connection of 2wire
BEROs
possible
permitted quiescent
current
max. 1.5 mA