Digital Electronic Modules
11-84
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Technical specifications
Dimensions and weight
Dimensions W x H x D 15 x 81 x 52 (mm)
Weight Approx. 50 g
Module-specific data
Supports clock
synchronized mode
No
Number of outputs 2
Cable length
Unshielded max. 600 m (164 ft)
shielded max. 1,000 m
(164 ft)
Voltages, currents, electrical potentials
Rated power supply voltage
L+ (from power module)
24 VDC
Reverse polarity protection
current per channel
Yes
up to 50°C Ma x . 5 A
to 60°C Max. 4 A
Electrical isolation
Between the channels Yes
Between channels and
backplane bus
Yes
Between channels and
power supply voltage
Yes
Between power supply
voltage and backplane
bus
Yes
Approved potential
difference
Between power supply
voltage and backplane
bus
75 VDC, 60 VAC
Between channels and
backplane bus
240 VAC
Between channels and
power supply voltage
240 VAC
Isolation tested
Between power supply
voltage and backplane
bus
500 VDC
Between channels and
backplane bus
2500 VDC
Between channels and
power supply voltage
2500 VDC
Current consumption
From power
supply L+
max. 30 mA
From the backplane bus max. 10 mA
Power loss of the module Typical 0.6 W
Status, interrupts, diagnostics
Status display Green LEDs pro
Channel
Diagnostic functions No
Data for Selecting an Actuator
Output current
Continuous thermal
current
Max. 5 A
Minimum load current 8mA
Connecting 2 outputs in
parallel
For redundant triggering
of a load
No
To increase
performance
No
Actuation of a digital input Yes
Switching frequency
with ohmic load 2Hz
with inductive load 0.5 Hz
With lamp load
Limitation (internal) of the
inductive disconnection
voltage
Short-circuit protection of
the output
1)
2Hz
No
No
1)
The relay outputs must be externally fused with
6A.
When installed in a hazardous zone as per the
National Electric Code (NEC) the fuse must
only be removed with a suitable tool if the
module is not in the explosive zone.