Digital Electronic Modules
11-86
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Table 11-29 Switching c apacity and service life of contacts, continued
Resistive load Operating
cycles (typical)
NC contacts
Operating
cycles (typical)
NO contacts
CurrentVoltage
With inductive load
24 VDC 2.0 A 0.1 million 0.1 million
as per IEC
947-5-1
DC 13
C
1.0 A 0.2 million 0.2 million
-
-
,
15
0.5 A 0.5 million 0.5 million
48 V DC 2.0 A 0.07 million 0.05 million
1.0 A 0.15 million 0.1 million
0.5 A 0.4 million 0.25 million
48 VAC 1.0 A 0.5 million 0.3 million
60 VAC 1.0 A 0.5 million 0.3 million
120 VAC 2.0 A 0.1 million 0.1 million
1.0 A 0.3 million 0.1 million
0.5 A 0.9 million 0.6 million
0,1 A 1.5 million 1.0 million
230 VAC 2.0 A 0.1 million 0.1 million
1.0 A 0.5 million 0.3 million
0.5 A 0.9 million 0.6 million
0.1 A 1.0 million 1.0 million