Analog Electronic Modules
12-7
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Measuring ranges for resistive sensors: 150 Ω, 300 Ω, 600 Ω, 3000 Ω
Table 12-7 SIMATIC S7 Format: Measuring ranges 150
Ω
, 300 Ω, 600 Ω, 3000 Ω
Measuring
Measuring Measuring Measuring Units
range
150 Ω
range
300 Ω
range
600 Ω
range
3000 Ω
decimal hexadeci -
mal
Area
> 176.38 > 352,77 > 705,53 > 3527,67 32767 7FFF
H
Overflow
176,38 352,77 705,53 3527,67 32511 7EFF
H
: : : : : :
Overshoot
150,005 300,01 600,02 3000,11 27649 6C01
H
150,00 300,00 600,00 3000,00 27648 6C00
H
112,50 225,00 450,00 2250,00 20736 5100
H
: : : : : : Nominal
range
0,00 0,00 0,00 0,00 0 0
H
-- 1 FFFF
H
(negative values are not physically possible)
: :
Undershoot
ran
e
--4864 ED00
H
--32768 8000
H
Underflow*
* With faulty connection of terminators