Analog Electronic Modules
12-106
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Analog Value Formation
Resolution (including sign)
¦
10 V/ 16 Bit
1to5V/14bits
Conversion time (per
channel)
Max. 1.0 ms
Settling time
For resistive load 0.1 ms
For capacitive load 0.5 ms
For inductive load 0.5 ms
Interference Suppression, Error Limits
Crosstalk between outputs >60dB
Operational error limits
(across the temperature
range, in relation to output
range)
0.07 %
Basic error limit (operational
error limit at 25 _C, related
to the output range)
0.03 %
Temperature error (in
relation to output range)
0.001 %/K
Linearity error (in relation to
output range)
0.02 %
Repetition accuracy (in
transient state at 25 _C,
relative to output range)
0.01 %
Output ripple, bandwidth 0
to 50 kHz (in relation to
output range)
0.02 %
Data for selection of the actuator
Output range (nominal
value)
10 V
1to5V
Load impedance (in the
nominal range of the
output)
With voltage
outputs
Min. 1.0 k
Capacitive load max. 1 µF
Voltage output
Short-circuit protection Yes
Short-circuit current Approx. 25 mA
Destruction limit for
externally applied
voltages/currents
Voltage measured
between the outputs
and M
ANA
Max. 15 V
continuous, 75 V for
max. 1 s (sampling
ratio 1:20)
Current ma x . DC 50 mA
Connection of actuators
Voltage output
2-wire connection Possible, without
compensation of
cable resistance
4-wire connection possible

Table of Contents