Analog Electronic Modules
12-114
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Analog Value Formation
Resolution (including sign)
¦
20 mA/ 16 Bit
4to20mA/15bits
Conversion time (per
channel)
Max. 1.0 ms
Settling time
For resistive load 0.25 ms
For capacitive load 1.0 ms
For inductive load 0.5 ms
Interference Suppression, Error Limits
Crosstalk between outputs >60dB
Operational error limits
(across the temperature
range, in relation to output
range)
0.07 %
(at 250 load
resistance)
0.3 %
(at all other load
resistances)
Basic error limit
(operational error limit at
25 _C, related to the input
range)
0.03 %
(at 250 load
resistance)
0.26 %
(at all other load
resistances)
Temperature error (in
relation to output range)
0.001 %/K
Linearity error (in relation
to output range)
0.02 %
Repetition accuracy
(in transient state at 25 _C,
relative to output range)
0.01 %
Output ripple (in relation to
output range, bandwidth 0
to 50 kHz)
0.02 %
Data for selection of the actuator
Output range (nominal
value)
20 mA
4to20mA
Load impedance (in the
nominal range of the
output)
For current outputs max. 500
For inductive load 1mH
Current output
No-load voltage 18 V
Destruction limit for
externally applied
voltages/currents
Voltage measured
between the outputs
and M
ANA
Max. 15 V
continuous; 75 V for
max. 1 s (sampling
ratio 1:20)
Current max . DC 50 mA
Connection of actuators
Current output
2-wire connection
possible