Brief Instructions on Commissioning ET 200S
2-14
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Configuration
1. Start SIMATIC Manager, and create a new project with an I/O controller
(CPU 317-2 PN/DP, for example). Create OB 1, OB 82 and OB 83 for the
project.
2. In HW CONFIG open the window Properties -- Ethernet interface and create
a subnet, for example, Ethernet(1).
3. From the hardware catalog add the IM151-3 PN from the ET 200S catalog on
Ethernet(1):PROFINET IO system (100).
4. Drag the various ET 200S modules from the hardware catalog to the
configuration table.
Table 2-2 Configuration table in HW CONFIG for PROFINET IO
Module
Order number I
address
O
address
Comment
0 6ES7 151-3AA00-0AB0 IM151-3 PN
1 6ES7 138-4CA00-0AA0 PM-E 24 VDC Power module
2 6ES7 131-4BB00-0AB0 2DI 24 VDC 0 Bits 0.0 and 0.1
3 6ES7 131-4BB00-0AB0 2DI 24 VDC 1 Bits 1.0 and 1.1
4 6ES7 131-4BB00-0AB0 2DI 24 VDC 2 Bits 2.0 and 2.1
5 6ES7 131-4BB00-0AB0 2DI 24 VDC 3 Bits 3.0 and 3.1
6 6ES7 138-4CA00-0AA0 PM-E 24 VDC Power module
7 6ES7 132-4BB00-0AB0 2DO 24 VDC 0 Bits 0.0 and 0.1
8 6ES7 132-4BB00-0AB0 2DO 24 VDC 1 Bits 1.0 and 1.1
9 6ES7 132-4BB00-0AB0 2DO 24 VDC 2 Bits 2.0 and 2.1
10 6ES7 132-4BB00-0AB0 2DO 24 VDC 3 Bits 3.0 and 3.1
5. Set the following parameters:
-- In the properties IO device dialog box for the PM-E 24 VDC,
module 1 (in the configuration table)
Diagnosis: Load voltage not present
-- In the I/O device properties dialog box for 2 DO 24 VDC,
Module 7 (in the configuration table)
Diagnosis: wire break A0
6. Compile and save the configuration.