Special Measures for Interference-Free Operation
F-3
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Wiring of DC-operated coils
DC-operated coils are wired with diodes and Zener diodes as illustrated in the
following figure.
+
--
+
--
With diode With Zener diode
Figure F-2 Wiring of DC-operated coils
A circuit with diodes/Zener diodes has the following features:
Switching overvoltages can be completely avoided.
A Zener diode has higher circuit interruption voltage.
Long switch-off delay (6 to 9 times longer than without a protective circuit).
A Zener diode switches off quicker than a diode circuit
Wiring of AC-operated coils
AC-operated coils are wired with varistors or RC elements as illustrated in the
figure.
With varistor With RC element
~
~
~
~
Figure F-3 Wiring of AC-operated coils
A circuit with a varistor has the following features:
The amplitude of the switching overvoltage is limited but not dampened.
The gradient of the overvoltage remains the same.
The switch-off delay is short.
A circuit with RC elements has the following properties:
The amplitude and gradient of the switching overvoltage are reduced.
The switch-off delay is short.