Glossary
Glossary-7
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
PROFINET components
A PROFINET component includes the complete data of the hardware
configuration, the parameters of the modules, and the associated user program.
The PROFINET component consists of the following:
Technological function
The (optional) technological (software) function includes the interface to other
PROFINET components in the form of switchable inputs and outputs.
Device
The device is the manifestation of the physical automation device or field device,
including the distributed devices, sensors and actuators, mechanics, and the
device firmware.
PROFINET device
A PROFINET device always has at least one Industrial Ethernet terminal. A
PROFINET device can also have a PROFIBUS terminal and can act as a master
with proxy functions. In exceptional cases a PROFINET device can also have
multiple PROFIBUS terminals (such as CP 5614).
PROFINET I/O
PROFINET I/O as a subset of PROFINET is a communications concept for the
implementation of modular , distributed applications.
PROFINET I/O can be used to establish automation solutions similar to those
known and made familiar under PROFIBUS.
PROFINET I/O is implemented by the PROFINET standard for automatic devices
and also by the STEP 7 engineering tool.
This means that in STEP 7 you have the same application view -- regardless of
whether you are configuring PROFINET devices or PROFIBUS devices.
You program your user program in the same way for both PROFINET I/O and
PROFIBUS DP if you use the blocks and system status lists enhanced for
PROFINET I/O.
PROFINET I/O Controller
Device that is addressed via the connected I/O devices. This means that the I/O
controller exchanges input and output signals with associated field devices. With
the I/O controller this often means the controller in which the automation program
is running.
PROFINET I/O device
Distributed field device to which the I/O controller is assigned (for example, remote
I/O, valve blocks, frequency converter, switches)