Brief Instructions on Commissioning ET 200S
2-17
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Interrupts, for example, removing and inserting the 2 DI 24 VDC High Feature
digital electronic module
1. Remove the 2 DI 24 VDC High Feature electronic module (e.g. from slot 2)
from the terminal module during operation.
2. Watch the status LEDs on the IM 151-3 PN:
-- SF: lit ⇒ diagnostic message exists.
-- B F : O f f
-- ON: lit
Result: The ET 200S continues to operate problem-free.
3. OB 83 is started in the event of a remove interrupt. In OB 83 start SFB 52.
Evaluate the diagnostic data set E002
H
.
Byte Contents Meaning
Header information
0 and 1 8104
H
Data record with discrepancies between the expected and
actual configuration
2 and 3 0014
H
20 bytes follow
4 and 5 0100
H
Version 1.0
6 and 7 0001
H
0001
H
if the preset deviates from the actual configuration
IO device header information
8 and 9 0000
H
Fixed
10 and 11 0000
H
Fixed
12 and 13 0001
H
Number of slots in which there is a discrepancy between the
expected and actual configuration
Configuration data of slots
14 and 15 0002
H
Slot number of the slot with a discrepancy between
expected and actual configuration
16 to 19 XXXXXXXX
H
Identification of the inserted module
20 and 21 0000
H
No module inserted
22 and 23 0000
H
Number of submodule slots with preset/actual deviation
Because the content is 0000
H
, there are no additional
submodule data.