01/2007
6.2 Commissioning
6-135
© Siemens AG 2007 All Rights Reserved
SINUMERIK 840Di sl Manual (HBIsl) – 01/2007 Edition
6.2.2 External communications link: Ethernet
To load the configuration from an external computer (PG/PC) into the
SINUMERIK 840Di sl PLC via an Ethernet connection, the following conditions
must be met on the PG/PC:
S Ethernet communication is possible in principle or set up
S PG/PC interface is parameterized (see below)
S The PG/PC is connected to one of the Ethernet interfaces of the
SINUMERIK 840Di sl PCU (Ethernet 1: company network or Ethernet 2:
local network)
The PG/PC interface is parameterized in the SIMATIC Manager via menu item:
Options > Set PG/PC interface...:
Dialog box: Set PG/PC interface
tab: Access path
Interface parameterization used: <Interface>
OK
Notice
Do not select ISO interfaces as Ethernet interfaces from the list of interfaces,
e.g. ”ISO Ind. Ethernet –> Realtek RTL8139...”.
Instead, use the appropriate TCP/IP interfaces, e.g. ”TCP/IP –> Realtek
RTL8139...”.
6.2.3 External communications link: MPI/PROFIBUS
To load the configuration from an external computer (PG/PC) into the
SINUMERIK 840Di sl PLC via an MPI connection, the following conditions must
be met on the PG/PC:
S Communications module (alternative):
– CP5611: MPI/PROFIBUS communications processor (PCI)
– CP5511: MPI/PROFIBUS communications processor (PCMCIA)
S MPI/PROFIBUS driver is installed
S PG/PC interface is parameterized (see below)
S The MPI/PROFIBUS interface of the CP is linked to the MPI/PROFIBUS
interface of the MCI board (X1).
The PG/PC interface is parameterized in the SIMATIC Manager via menu item:
Options > Set PG/PC interface...:
PG/PC interface
Dialog box
PG/PC interface
6 PLC Commissionin