11.7 Digital and analog I/O devices
11-394
© Siemens AG 2007 All Rights Reserved
SINUMERIK 840Di sl Manual (HBIsl) – 01/2007 Edition
R Computational time of position controller and/or signal module
Dx Exchange of user data between DP master and DP slaves
MSG Acyclic services (e.g. DP/V1, pass token)
RES Reserve: ”active break” until the equidistant cycle has elapsed
1
Set the system variables, e.g. $A_OUT[8] in the part program or
synchronized action
2
Transmit the output signal to the signal module on
PROFIBUS DP
3
Connect the signal to the output of the module.
11.7.6 Configuration example
In the following configuration example, the following digital input/outputs are
available to the NCK:
ET200
24 digital inputs
16 digital outputs
ADI4
8 digital inputs
16 digital outputs
Note
S The I/O addresses of the modules are assigned automatically by ”HW
Config” (manual adjustment is possible).
S Each I/O address refers to an input/output byte.
PROFIBUS(2): DP master system (2)
840Di sl (configuration) –– 840Di sl_ET200_ADI4
(0) UR
X2
PLC317–2DP M/S 2AJ10
DP master
2
4
CP 342–5
(5) IM 153 (6) ADI4
Fig. 11-33 Example configuration: SINUMERIK 840Di sl with ET200 and ADI4
11 NCK Commissionin
g
with HMI Advanced