6.3 Creating a SIMATIC S7 project
6-147
© Siemens AG 2007 All Rights Reserved
SINUMERIK 840Di sl Manual (HBIsl) – 01/2007 Edition
6.3.9 Networking PG/PC and PCU (Ethernet)
In order that external components connected via Ethernet, e.g. PG/PC with the
SINAMICS drive commissioning tool STARTER or SIMATIC Step 7, can com-
municate with SINUMERIK 840Di sl and SIMATIC drive units, the PG/PC must
be linked to the PCU in the S7 project.
Perform the following actions for networking:
1. Start the NetPro configuration tool in HW Config.
HW Config – [SINUMERIK (configuration) –– SIN840Di sl]
Station Edit Insert Target System View Tools Window Help
(0) 840Di sl
PROFIBUS(1): DP master system(1)
2 PLC 317–2DP 2AJ10
2. From the selection list of the network objects, open Stations and insert a
PG/PC into the project (1).
NetPro – [SIN840Di sl (network) –– C:\Program
Files\...\s7proj\SIN840_sl]
Find
Ready
Selecting the network objects
PROFINET IO
TCP/IP –> Realtek TRL813
Programming device or
PC
1
Network Edit Insert Target System View Tools Window Help
PROFIBUS PA
PROFIBUS DP
Stations
Subnets
SIMATIC S5
SIMATIC PC Station
SIMATIC 300
PG/PC
Other stations
SIMATIC DP
SIMATIC H Station
SIMATIC 400
3. Double–click the inserted station: PG/PC to open the Properties dialog box.
Select the tab: Interface (1). Click the button: New... to open the dialog box
for creating a new interface (2). Select the interface type: Industrial Ethernet
(3) . Click OK to confirm the dialog.
Execution
6 PLC Commissionin
g