10.1 SIMODRIVE 611 universal/E, POSMO CD/CA and SI
10-281
© Siemens AG 2007 All Rights Reserved
SINUMERIK 840Di sl Manual (HBIsl) – 01/2007 Edition
10.1.6 Setting the routing information
Setting the routing information:
MPI address of the PLC
PROFIBUS subnet ID
The easiest method to do so is the expert mode after resetting the routing infor-
mation.
Notice
To use the PLC as a router between MPI and PROFIBUS DP, the MPI
networking of the PLC must be parameterized in the S7 project. See Section
6.3.3, Page 6-141.
Button: Reset routing information...
Radio button: Export mode
MPI No: 2 (see note)
PROFIBUS: <Subnet ID> (see below)
OK or Go online
Notice
With SINUMERIK 840Di sl, the routing of the MPI interface to the PROFIBUS
DP is provided by the PLC. Therefore, the MPI address of the PLC must be
specified as the ”MPI No”.
With SINUMERIK 840Di sl, the PLC always has the MPI address 2.
Enter the 8–digit PROFIBUS S7 subnet ID of DP master (S7 project) in the
12–digit input form of the SimoCom U dialog box as follows:
Example:
S7 project: 8–digit S7 subnet ID:
0010 0005
SimoCom U: 12–digit S7 subnet ID:
1000 05000000
If you do not have the PROFIBUS S7 subnet ID, you can call it using the
SIMATIC Manager STEP 7.
To do so, proceed as follows:
S Open the appropriate S7 project in the SIMATIC Manager S7.
S Select the appropriate station (in the example project: SIMATIC 300)
SimoCom U
dialog box:
End
PROFIBUS S7
subnet ID
entering
PROFIBUS S7
subnet ID
determining