01/2007
11.11NCK/PLC diagnostics
11-411
© Siemens AG 2007 All Rights Reserved
SINUMERIK 840Di sl Manual (HBIsl) -- 01/2007 Edition
S Signal input for shutdown behavior: Signal level
This selection field is for c onfiguring the level of the shutdown signal of the UPS:
S Low active
Upon detection of the low level (0) at the configured input, first the
SINUMERIK 840Di sl NCK/PLC and then Windows XP are closed.
S High active
Upon detection of the high level (1) at the configured input, first the
SINUMERIK 840Di sl NCK/PLC and then Windows XP are closed.
To apply the changes you have made, press the ”Accept softkey. The message
box that is then displayed has to be acknowledged again with the ”Accept” softkey.
The ”Cancel softkey rejects all changes and displays the original settings
again.
2560 KB RAM/HD backed up
MPF0
Program aborted
ROV
CHAN1 JOG Ref
Commiss--
ioning
Cancel
Signal level
Channel RESET
Diagnostics Settings
Settings
Non--volatile user memory
Signal source
Signal input for shutdown behavior
deactivated
--
Accept
Accepting the changes can lead to loss of NC user data.
Make sure that this data has been stored in a series startup file.
1. Memory settings have been changed.
Changes will not take effect until the system is rebooted.
2. The shutdown response has been changed.
Incorrect configuration will result in loss of data if there is a power failure.
Do you really want to accept the changes?
Settings
Fig. 11-36 Making settings
Notice
We urgently recommend creating a series startup file before changing the data
described above. See Section 15, Page 15-459.