EasyManuals Logo

Symmetricom TimeHub 5500 Reference Guide

Symmetricom TimeHub 5500
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #136 background imageLoading...
Page #136 background image
Keywords
Keyword Description
136 TimeHub 5500 TL1 Reference Guide 097-55501-02 Issue 7 – January, 2005
SNGCLK (Single Clock)
This keyword allows establishment of alarm behavior associated with single Clock
card operation. If normal operation for a shelf is with a single Clock card
(non-redundant operation), it may be preferable to establish a non-alarm for this
condition by setting the keyword to Y. The keyword format is:
SNGCLK=<value>
Command Example (for setting single clock operation as normal operating mode):
ED-EQPT::IMC:SC01:::SNGCLK=Y;
Response Example:
SYMMBITS 01-06-19 08:09:52
M SC01 COMPLD
;
Command Example (for retrieving SNGCLK setting):
RTRV-EQPT::IMC:SC02:::PARAMETER=SNGCLK;
Response Example:
SYMMBITS 01-06-19 08:11:09
M SC02 COMPLD
"IMC::SNGCLK=Y"
;
Parameter Value Description
<value> Y Single Clock card operation does not generate
an alarm
N Single Clock card operation generates an alarm