097-55501-02 Issue 7 – January, 2005 TimeHub 5500 TL1 Reference Guide 77
Commands
Command Description
Command Example:
RTRV-TH::CLK-2:SC1::LMRTIE-15M;
The command in this example displays the threshold value set for the LMRTIE-15M
measurement on input channel 2.
Retrieve User
This command displays the currently logged in user’s access level. The command
format is:
RTRV-USER:::<ctag>;
Command Example:
RTRV-USER:::SC1;
The command in this example displays the currently logged in user’s access level.
Parameter Value Variables Description
<aid> CLK — Use for SPRD measurements only
CLK-a a = 1 to 4 Input port number of Clock card
<montype> FFOF-a a = 3S, 12S, 48S, 192S,
768S, 3072S
FFOF monitored type, where a is the
averaging time interval in seconds
LMRTIE-a a = 1S, 1M, 15M, 30M,
1H, 2H, 8H, 24H
LMRTIE monitored type, where a is
the observation time interval in
seconds (S), minutes (M), or hours
(H)
MRTIE-a a = 1S, 1M, 15M, 30M,
1H, 2H, 8H, 24H
MRTIE monitored type, where a is the
observation time interval in seconds
(S), minutes (M), or hours (H)
SPRD-a a = 3S, 12S, 48S, 192S,
768S, 3072S
SPRD monitored type, where a is the
averaging time interval in seconds
TDEV-a a = 1S, 4S, 16S, 64S,
256S, 1024S
TDEV monitored type, where a is the
averaging time interval in seconds
TIE-a a = 1S, 1M, 15M, 30M,
1H, 2H, 8H, 24H
TIE monitored type, where a is the
observation time interval in seconds
(S), minutes (M), or hours (H)