Fig. 76: Time-dependent voltage monitoring
P1 0.00 s → 45.0 % P2 0.15 s → 45.0 % P3 0.15 s → 70.0 %
P4 0.7 s → 70.0 % P5 1.50 s → 90.0 % P6 3.00 s → 90.0 %
P7 4.00 s → 90.0 %
Fallback
threshold
90.0 % Initial
threshold
80.0 % Fallback
time
1.00 s
ID Parameter CL Setting range
[Default]
Description
4950 Monitoring 2 On Time-dependent voltage monitoring is
carried out according to the following
parameters.
[O] No monitoring is carried out.
4952 AND characteristics 2 On Each phase falls below/exceeds the
threshold for tripping.
[O] At least one phase falls below/exceeds
the threshold for tripping.
123LS-5 v2 Series37650
4 Conguration
4.3 Congure Monitoring