the fault condition is no longer
detected.
The alarm must be acknowledged and
reset by manually pressing the
appropriate buttons or by activating
the LogicsManager output "External
acknowledgement" (via a discrete
input or via an interface).
2994 Monitoring lockable 2 Yes Monitoring for fault conditions is only
performed if "Lock Monitoring Status
24.40 is false".
[No] Monitoring for this fault condition is
continuously enabled regardless of
"Lock Monitoring Status 24.40".
4.3.5 Operating range
General notes
The operating range monitoring signalizes a wrong behavior of the system. The device is
blocked to continue. The reason for this often is a not reached operating range or a
missing breaker feedback or release. The device indicates the root cause by issuing an
additional error number. Each error number represents a dierent root cause. This shall
provide assistance in troubleshooting.
If this protective function is triggered, the display indicates "Operating range {x}" and
the following logical command variable will be enabled:
If there is more than one failure at the same time following operating range priority is
used:
1 - 2 - 4 - 3 - 6 - 5
Command variable Function Conditions to trigger the alarm
08.48 Operating range 1 CAN interface
The LS-5 needs at least one other
member. The alarm indicates that
the LS-5 is blocked, because there
is no other member on the CAN
bus recognized.
•
The command LM "Enable CBA to close" is
TRUE
• AND The CBA feedback is open
• AND No CAN member is recognized
OR
• The command LM "Enable CBB to close" is
TRUE
• AND The CBB feedback is open
•
AND No CAN member is recognized
Notes
This alarm is only active if the
application mode CBA/CBB
(parameter 8992) is congured to
"LS-5".
08.49 Operating range 2 Synchronous networks
The alarm indicates that the LS-5
is blocked, because there are
synchronous networks or
synchronous segment numbers
on system A and system B side
recognized. But the according
congurations "Connect
•
The command LM "Enable CBA to close" is
TRUE
• AND The CBA feedback is open
• AND Synchronous mains or synchronous
segments are detected but not allowed to
connect.
141LS-5 v2 Series37650
4 Conguration
4.3 Congure Monitoring