Parameter ID
Mains voltage increase 8806
The mains current and power measurement is never used in the application mode
A07
.
6.4.2.3 Setup Mains Decoupling With easYgen
Overview
To provide mains decoupling, acting on the GCB, the mains decoupling function of the
easYgen must be used.
Prerequisites easYgen
Personnel: Quali󰈡ed electrician
Ensure the following prerequisites are met:
1. ▷
The mains measurement is connected together with the busbar measurement on the
generator busbar.
Con󰂢gure easYgen
For detailed information on the easYgen
con󰈡guration, refer to the easYgen-3400/3500 or
easYgen-3400XT/3500XT manual.
For matching the VDE-AR-N 4105 requirements, please refer to the 4105 chapters in the
easYgen and the LS-5 manual.
6.4.2.4 Setup Mains Decoupling With LS-5
Overview
In this setup the mains decoupling is provided by the LS-5 for the MCB.
When the mains decoupling over GCB is required, refer to
╚═▷ “6.4.2.3 Setup Mains
Decoupling With easYgen.
The LS-5(s) which are responsible for the mains breakers take over the mains monitoring
and execute the decoupling function.
269LS-5 v2 Series37650
6 Application
6.4 Setup easYgen & Independent LS-5x2 Applications (Mode A02)
Released