[B] what action should be taken when the
limit is surpassed.
Notes
For additional information refer to ╚═▷
“9.4.1 Alarm Classes”
8837 Self acknowledge 2 Yes The control unit automatically clears
the alarm if the fault condition is no
longer detected.
[No] The control unit does not
automatically reset the alarm when
the fault condition is no longer
detected.
The alarm must be acknowledged and
reset by manually pressing the
appropriate buttons or by activating
the LogicsManager output "External
acknowledgement" (via a discrete
input or via an interface).
8846 Monitoring lockable 2 Yes Monitoring for fault conditions is only
performed if "Lock Monitoring Status
24.40 is false."
[No] Monitoring for this fault condition is
continuously enabled regardless of
"Lock Monitoring Status 24.40".
4.3.3.4 CBB
General notes
Circuit breaker monitoring contains two alarms: A "breaker close" alarm and a "breaker
open" alarm.
"Breaker close alarm"
If the control initiates a close of the breaker and the breaker fails to close after the
con󰈡gured number of attempts the monitoring CBB alarm will be initiated (refer to
parameter "CBB maximum attempts of closure", parameter
3418).
If this protective function is triggered, the display indicates "CBB fail to close" and the
logical command variable "08.05" will be enabled.
"Breaker open alarm"
If the control is attempting to open the circuit breaker and it fails to see that the CBB is
open within the con󰈡gured time in seconds after issuing the breaker open command then
the monitoring CBB alarm will be initiated (refer to parameter "CBB open monitoring",
parameter 3420).
If this protective function is triggered, the display indicates "CBB fail to open" and the
logical command variable "08.06" will be enabled.
134 LS-5 v2 Series 37650
4 Con󰈡guration
4.3 Con󰈡gure Monitoring
Released