conguration is the maximum
allowed slip frequency then
generator(s) can run faster than
system A.
• If the system A is the variable
system (i.e. generator), this
conguration is the maximum
allowed slip frequency then
generator(s) can run slower than
system B.
5700 Voltage dierential CBB 2 0.50 to 20.00 %
[5.00 %]
The maximum permissible voltage
dierential for closing CBB is
congured here.
Notes
If the dierence between system A
and system B voltage does not exceed
the value congured here and the
system voltages are within the
operating voltage windows
(parameters
5800 / 5801 / 5810 /
5811), the command: "CBB close"
may be issued.
4.4.2.4.2 Phase Matching CBB
The following parameters are only valid if 'Synchronization CBB' (parameter
5729) is
congured to 'Phase matching'.
ID Parameter CL Setting range
[Default]
Description
5703 Max. positive phase angle CBB 2 0.0 to 60.0 °
[7.0 °]
The prerequisite for a connect
command being issued for the CBB is
that the leading phase angle between
system B and system A is below the
congured maximum permissible
angle.
5704 Max. negative phase angle CBB 2 -60.0 to 0.0 °
[-7.0 °]
The prerequisite for a connect
command being issued for the CBB is
that the lagging phase angle between
system B and system A is above the
congured minimum permissible
angle.
5707 Phase matching CBB dwell time 2 0.0 to 60.0 s
[3.0 s]
This is the minimum time that the
system A/B voltage, frequency, and
phase angle must be within the
congured limits before the breaker
will be closed.
166 LS-5 v2 Series 37650
4 Conguration
4.4 Congure Application