The three phase synchronization is used if following conditions are active
• System A voltage measurement is congured to a three phase system
(Parameter 1851)
• System B voltage measurement is congured to a three phase system
(Parameter 1853)
• Synchronization is congured as 3-phase (Parameter 8817)
The synchronization type can be set on single or three phase matching.
If the measurement system is congured on three phase and the 1-phase
synchronization is selected the operating ranges are still three phase considered
ID Parameter CL Setting range
[Default]
Description
8817 Synchronization 2 This parameter selects the single phase or three
phase synchronization.
[1-phase] The synchronization function
compares the L1-L2
measurement system A to
system B.
3-phase The synchronization function
compares the L1-L2, L2-L3, L3-
L1 measurement system A to
system B.
12906 Syn. mode CHECK
(Synchronization mode CHECK)
2 Determined by
LogicsManager
[(0&1)&1]
Once the conditions of the
LogicsManager have been fullled the
CHECK synchronization mode will be
enabled.
Notes
For information on the LogicsManager
and its default settings see ╚═▷ “9.3.1
LogicsManager Overview”.
12907 Syn. mode PERM.
(Synchronization mode PERMISSIVE)
2 Determined by
LogicsManager
[(0&1)&1]
Once the conditions of the
LogicsManager have been fullled the
PERMISSIVE synchronization mode will
be enabled.
Notes
For information on the LogicsManager
and its default settings see ╚═▷ “9.3.1
LogicsManager Overview”.
12908 Syn. mode RUN 2 Determined by
LogicsManager
Once the conditions of the
LogicsManager have been fullled the