[1]
Notes
In example: Segment no. 10
No access in the application mode
A05
.
8811 Segment number Sy.B 2 1 to 64
[2]
Segment number for system B.
Notes
In example: Segment no. 12
No access in the application mode
A05
.
8799 Segment number load 2 1 to 64
[3]
Segment number for the load path.
Notes
In example: Segment no. 11
No access in the application mode
A05
.
8813 Mains pow. measurem. 2 [Valid] The measured power is used for mains
real power control.
Invalid The measured power is not used for
power control.
Notes
No access in the application mode
A05
.
8814 Mains connection 2 None No system is wired to mains directly. It
can not be used for mains failure
detection.
[System A] System A is wired to mains directly.
System B System B is wired to mains directly.
Isol. swi. The system of the isolation switch is
wired to mains.
Notes
No access in the application mode
A05
.
8816 Variable system 2 One of the systems must be dened
as a variable system. A variable
system is dened as a system that
can change in frequency and voltage
due to the easYgen control unit. In
normal applications this is the
frequency/voltage that is situated
179LS-5 v2 Series37650
4 Conguration
4.4 Congure Application