Fig. 144: LS-5 Application mode
A02
(example)
The band width of the CAN bus allows to connect up to 32 easYgens in conjunction with
up to 16 LS-5 devices. This is always guaranteed. In particular cases it could be desired
to run more than 16 LS-5 devices. Theoretically up to 32 LS-5 are possible, but it requires
in return a reduced number of easYgen devices. A rule of thumb is that the total amount
of easYgens and LS-5s shall never expire 48 devices. To be on the safe side please
discuss the possible risks with the Woodward Sales Support.
General notes
The LS-5 is expecting at least one easYgen device in the system.
Depending on the complexity of the system equally complex external program logics
may be required.
265LS-5 v2 Series37650
6 Application
6.4 Setup easYgen & Independent LS-5x2 Applications (Mode A02)