CAN Para-
meter
ID
Description Multiplier Units Model
Data
byte 0
(Mux)
Data
byte
13255 = Open CB B
13340 = CB B request
13209 = CB B Dead bus closure
3 3,4,5,6 337 System A total active power AC measurement 1 W LS-5x1 v2,
LS-5x2 v2
4 1,2 10107 Discrete outputs 1 to 6
Relay-Output 1 (inverted) Mask: 8000h Bit LS-5x1 v2,
LS-5x2 v2
Relay-Output 2 Mask: 4000h Bit LS-5x1 v2,
LS-5x2 v2
Relay-Output 3 Mask: 2000h Bit LS-5x1 v2,
LS-5x2 v2
Relay-Output 4 Mask: 1000h Bit LS-5x1 v2,
LS-5x2 v2
Relay-Output 5 Mask: 0800h Bit LS-5x1 v2,
LS-5x2 v2
Relay-Output 6 Mask: 0400h Bit LS-5x1 v2,
LS-5x2 v2
internal Mask: 0200h Bit
internal Mask: 0100h Bit
internal Mask: 0080h Bit
internal Mask: 0040h Bit
internal Mask: 0020h Bit
internal Mask: 0010h Bit
internal Mask: 0008h Bit
internal Mask: 0004h Bit
internal Mask: 0002h Bit
internal Mask: 0001h Bit
4 3,4,5,6 185 System A current average 0.001 A LS-5x1 v2,
LS-5x2 v2
5 1,2 8018 internal Mask: 0001h Bit
internal Mask: 0002h Bit
internal Mask: 0004h Bit
internal Mask: 0008h Bit
internal Mask: 0010h Bit
internal Mask: 0020h Bit
internal Mask: 0040h Bit
internal Mask: 0080h Bit
28.01 Command to CB-control 1 (OR'ed) Mask: 0100h Bit LS-5x1 v2,
LS-5x2 v2
334 LS-5 v2 Series 37650
9 Appendix
9.2 Data Protocols