EasyManua.ls Logo

Woodward LS-5 v2 Series - Page 352

Woodward LS-5 v2 Series
448 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Load share bus communication - "fast" refreshed data
Mux Byte Bit Function Remark
4
Phase angle compensation is
incorporated
5 0 System A in range
1 System B in range
2 System A is black
3 System B is black
4 Breaker 1 closed
5 Breaker 2 closed
6 Synchronous networks detected Between system A an B
7 Not used
6 combi-
nations of
bits
below ...
During the breaker unload situation: If bit 3 »Execution of wish« is set together with
bit 0 »Wish to open the breaker«, the easYgen interprets this as an unload command.
During the breaker close situation (synchronization): If bit 3 »Execution of wish« is set
together with bit 1 »Wish to close the breaker«, the easYgen interprets this as a
synchronizing procedure.
If the 'Synchronization mode' is con󰈡gured to 'Slip frequency' and a separate slip
frequency o󰈠set is considered: bit 5 »Synchronization Mode« is "0", and bit
6 »Synchronization with separate slip frequency o󰈠set« is "1".
0 Wish to open the breaker
1 Wish to close the breaker
2 Wish is for breaker
0 = Breaker CBA
1 = Breaker CBB
3 Execution of wish The LS-5 informs that it will execute
the wish for close or open its
breaker. The execution wish isn't
active during dead bus closure or
immediately open from the breaker.
Notes
In application mode LS5
(multiple LS5) only:
This bit will be send only if all
of the additional conditions are
TRUE:
Synchronization mode is
RUN or CHECK
Di󰈠erent segment
number between system
A and B
Synchronous mains or
segment closing isn't
active
4 Variable system
0 = System A
1 = System B
Notes
The LS-5 informs that the "variable
system" is on side A or B.
352 LS-5 v2 Series 37650
9 Appendix
9.2 Data Protocols
Released

Table of Contents

Related product manuals