LS-5 ags
5 internal logical LS-5 ags may be programmed to activate/deactivate functions. This
permits more than 3 commands to be included in a logical function. They may be used
like "auxiliary ags".
These ags are transmitted on the CAN bus. The ags of all LS-5 are received (as 26.01 to
27.80) by the LS-5 and the easYgen. They can be used as inputs for the LogicsManager.
Name Function Number
Flag 1 LS5 LS5 ag 1 24.41
Flag 2 LS5 LS5 ag 2 24.42
Flag 3 LS5 LS5 ag 3 24.43
Flag 4 LS5 LS5 ag 4 24.44
Flag 5 LS5 LS5 ag 5 24.45
Internal functions
The following logical functions may be used to activate/deactivate functions.
Name Function Number
External acknowledge The alarm acknowledgement is performed from an external source
(parameter 12490)
00.15
Operation mode AUTO Activation of the AUTOMATIC operating mode (parameter
12510)
00.16
Operation mode MAN Activation of the MANUAL operating mode (parameter
12520)
00.17
Synchronization mode
CHECK
Used for checking a synchronizer prior to commissioning. The system actively
synchronizes generator(s) by issuing speed and voltage bias commands, but does
not issue a breaker closure command. (parameter 5728)
00.38
Synchronization mode
PERMISSIVE
The system acts in a synch check mode. The system will not issue speed or
voltage bias commands to achieve synchronization, but if synchronization
conditions are matched (frequency, phase, voltage and phase angle), the control
will issue a breaker close command. (parameter 5728)
00.39
Synchronization mode
RUN
Normal operating mode. The system actively synchronizes and issues breaker
closure commands. (parameter 5728)
00.40