Simple (function) Extended (conguration) Result
If TRUE, Transition mode 2 is enabled.
Deactivated by default.
Only available in application mode
A05
.
FALSE
[00.95] Lock keypad
If TRUE, the Lock keypad function is
activated.
Deactivated by default.
FALSE
Relay outputs
Simple (function) Extended (conguration) Result
[00.41] Relay 1 [R01] - Ready for operation OFF
Relay will be de-energized if unit is not ready
for operation or the logics manager output is
TRUE.
LM output is deactivated by default
The unit is only ready for operation after a
start-up delay following the power supply
connection.
FALSE
[00.42] Relay 2 [R02] - Horn / freely congurable
Relay energizes if the internal condition
"Horn" is TRUE
dependent on
Logics
Command
Variable
[01.12]
[00.43] Relay 3 [R03] - Command: open CBB / freely congurable
431LS-5 v2 Series37650
9 Appendix
9.3 LogicsManager Reference