1750 System rated frequency 2 50 / 60 Hz
[50 Hz]
The rated frequency of the system is
used as a reference 󰈡gure for all
frequency related functions, which use
a percentage value, like frequency
monitoring, breaker operation
windows or the Analog Manager.
1766 SyA. rated voltage 2 50 to 650000 V
[400 V]
The system A potential transformer
primary voltage is entered in this
parameter.
The system A rated voltage is used as
a reference 󰈡gure for all system A
voltage related functions, which use a
percentage value, like system A
voltage monitoring, breaker operation
windows or the Analog Manager.
1752 SyA. rated active power [kW] 2 0.5 to 99999.9 kW
[200.0 kW]
This value speci󰈡es the system A real
power rating, which is used as a
reference 󰈡gure for related functions.
1758 SyA. rated react. power [kvar] 2 0.5 to 99999.9 kvar
[200.0 kvar]
This value speci󰈡es the system A
reactive power rating, which is used
as a reference 󰈡gure for related
functions.
1754 SyA. rated current 2 1 to 32000 A
[300 A]
This value speci󰈡es the system A
rated current, which is used as a
reference 󰈡gure for related functions.
1768 SyB. rated voltage 2 50 to 650000 V
[400 V]
The system B potential transformer
primary voltage is entered in this
parameter.
The system B rated voltage is used as
a reference 󰈡gure for all system B
voltage related functions, which use a
percentage value, like system BS
voltage monitoring, breaker operation
windows or the Analog Manager.
1746 SyB. rated react. pwr.[kvar] 2 0.5 to 99999.9 kvar
[200.0 kvar]
This value speci󰈡es the system B
reactive power rating, which is used
as a reference 󰈡gure for related
functions.
1748 SyB. rated active power [kW] 2 0.5 to 99999.9 kW
[200.0 kW]
This value speci󰈡es the system B real
power rating, which is used as a
reference 󰈡gure for related functions.
1785 SyB. rated current 2 1 to 32000 A
[300 A]
This value speci󰈡es the system B
rated current, which is used as a
reference 󰈡gure for related functions.
1858 1Ph2W voltage measuring 2 [Phase - phase] The unit is con󰈡gured for measuring
phase-phase voltages if 1Ph 2W
measuring is selected.
87LS-5 v2 Series37650
4 Con󰈡guration
4.2 Con󰈡gure Measurement
Released