5.10 o: Operator Related Settings
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual 249
■ o2-04: Drive Model Selection
This parameter must be set when replacing the control board or the terminal board for any reason.
NOTICE: Drive performance will suffer if the correct drive capacity is not set to o2-04, and protective functions will fail to operate
properly.
Note: Change settings only when necessary.
■ o2-05: Frequency Reference Setting Method Selection
Determines if the ENTER key must be pressed after changing the frequency reference using the digital operator while in
the Drive Mode.
Setting 0: ENTER key required
Every time the frequency reference is changed using the digital operator, the ENTER key must be pressed for the drive to
accept the change.
Setting 1: ENTER key not required
The output frequency changes immediately when the reference is changed by the up or down arrow keys on the digital
operator. The ENTER key does not need to be pressed. The frequency reference (Fref) is saved to memory after
remaining unchanged for 5 seconds.
■
o2-06: Operation Selection when Digital Operator is Disconnected
Determines if the drive will stop when the digital operator is removed in LOCAL mode or when b1-02 or b1-16 is set to
0. When the operator is reconnected, the display will indicate that it was disconnected.
Setting 0: Continue operation
The operation is continued.
Setting 1: Trigger a fault
The operation is stopped and an “oPr” fault is triggered. The motor coasts to stop.
■
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up and the Run command is given from the
digital operator.
Note: This parameter is effective only when the Run command is set to be given from the digital operator (b1-02, b1-16 = 0).
Setting 0: Forward
Setting 1: Reverse
No. Name Setting Range Default
o2-04 Drive Model Selection -
Determined by drive
capacity
No. Name Setting Range Default
o2-05 Frequency Reference Setting Method Selection 0 or 1 0
No. Name Setting Range Default
o2-06 Digital Operator Disconnection Operation 0 or 1 0
No. Name Setting Range Default
o2-07 Motor Direction at Power Up when Using Operator 0 or 1 0