EasyManua.ls Logo

Agilent Technologies E6198B

Agilent Technologies E6198B
318 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-10 E6198B Switch/Load Unit User Manual
4 Configuring the Switch/Load Unit
Configuring the Current-Sense Jumpers
The Switch/Load Unit is shipped from the factory with the
current-sense jumpers J2 installed in the BUSSED position
forming one continuous current-sense bus along the
Switch/Load Unit backplane. These three jumpers have been
included so that, if necessary, the existing single current-sense
bus can be split up into as many as four independent
current-sense busses by changing the jumper location to SPLIT.
Each independent current-sense bus provides one reading, so
up to four simultaneous current-sense readings can be made at
a time.
The jumpers are located into J2 connector (Figure 3-7).
Removing any jumper splits the current-sense bus at that point.
Cards to the left of the removed jumper share a current-sense
bus isolated from the one shared by the cards on the right side
of the removed jumper.
The hardware allows each card to perform current-sense
measurements on only one channel at a time. However, it is
possible to command two cards sharing a common
current-sense bus to attempt simultaneous current-sense
readings. This can lead to a power bus to power bus short,
causing confused and incorrect readings.
Figure 4-11 shows the ISense Bussed/Split interface for
Standalone SLU. Toggle the switch to choose either Bussed or
Split mode.
Figure 4-11 ISense Bussed/Split Interface (Standalone SLU)

Table of Contents

Related product manuals