EasyManua.ls Logo

Allen-Bradley CompactLogix 5480

Allen-Bradley CompactLogix 5480
300 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 5069-UM002A-EN-P - January 2019 201
Develop Control Applications Chapter 8
When a timeout does occur, the controller produces the following warnings;
I/O Fault status information scrolls across the 4-character status display
of the controller.
A shows over the I/O configuration folder and over the devices that
have timed out.
A module fault code is produced. You can access the fault code via the
following:
The Module Properties dialog box
A GSV instruction
For more information about I/O faults, see the Logix 5000 Controllers Major,
Minor, and I/O Faults Programming Manual, publication
1756-PM014.
Determine If I/O Communication Has Timed Out
This example can be used with the CompactLogix 5480 controllers:
The GSV instruction gets the status of the I/O status indicator (via the
LEDStatus attribute of the Module object) and stores it in the
IO_LED tag.
IO_LED is a DINT tag that stores the status of the I/O status indicator
or status display on the front of the controller.
If IO_LED equals 2, at least one I/O connection has been lost and the
Fault_Alert is set.
Figure 40 - GSV Used to Identify I/O Timeout
!

Table of Contents

Other manuals for Allen-Bradley CompactLogix 5480

Related product manuals