3 608 878 300 Tightening Technology | Bosch Rexroth AG 303/641
System 350 | 3 608 878 300/2019-03
The field bus master must be programmed in a way that bytes 115 to 118 are evaluated as a torque value
for the second channel.
6.4.4.6 Example of results output with field bus
The following example is to clarify the assignment of the parameters and the results values.
The result is displayed in clear text in Figure 6–55; Figure 6–56 displays the contents of the storage area
in hexadecimals. The contents of the data buffer are assigned to the results in Table 6–54; the meaning
of the results is displayed in Table 6–55.
Fig. 6–55: Test of the results output via the System test CS field bus data function
Table 6–53:
Address
(length)
0 (4) 4 (82) 86 (7) 93 (15) 108 (15) 115 (4) 123 (15) 138
Control signal output
Application block
FO 1
Application result
in FO 2
1st channel result
from application
in FO 2
2nd channel result
from application
in FO 2
Actual torque
0:T
3rd channel result
from application
in FO 2
KE error
Example The last step of the tightening program was programmed with the following parameters:
Target function Torque 100 Nm
Monitoring function Torque:
Lower limit 98 Nm
Upper limit 102 Nm
Target function Angle:
Lower limit 50 degrees
Upper limit 250 degrees
IMpdp interface:
Number of I/O points: 16I+16O
Receive data 16 bytes
Send data 103 bytes