410/641 Bosch Rexroth AG | Tightening Technology 3 608 878 300
System 350 | 3 608 878 300/2019-03
6.7.7.13 Visualization messages
MID 0110 Show user text on LC display
MID 0111 TFT graphics display of user text
MID 0111 revision 001
Sent by:
superordinate computer
The CS351E-D (IL) or CS351S-D (IL) can generate text on the LC display by sending this message. The data field
may be max. four bytes long (if it is shorter than four characters: fill with space characters 0x20).
Note: -
Revision: 001 (supported by Rexroth OP)
Data field: User text with max. 4 ASCII characters, 4 bytes
Possible response MID Error no. Comment
Command accepted 0005 –
Command error 0004 01 Invalid data
Sent by: superordinate computer
The CS351E-G (IL) or CS351S-G (IL) can generate text on the TFT display by sending this message. The user can
also specify a time for the text to be displayed and whether the text has to be confirmed by the operator.
Note: -
Revision:
001 (supported by Rexroth OP and Rexroth OP-BMW)
Data field: data 117 bytes. Divided into four lines, each with 25 ASCII characters. Lines with less than 25
characters must be filled with space characters (0x20).
Possible responses MID Error no. Comment
Command accepted 0005 –
Command error 0004 01 Invalid data
Table 6–111: MID 0111 revision 001
Parameter Comments Bytes
Display duration Time in seconds that the text should be displayed.
The value consists of four ASCII characters.
ID 01
2
Value range 0000 – 9999
Presetting -
Example:
Display duration 60
Value 0060
4
Deletion condition – 0: Hide text after display duration or after clicking the OK-button
– 1: OK button must be clicked (display duration parameter is ignored)
The value consists of one ASCII character.
ID 2
2
Value range 0–1
Presetting -
Example:
Deletion
condition
Hide text after display duration or after clicking the
OK button
Value 0
1