FI002K0018v1100UK – THS/21 Instruction manual for installation, use and maintenance
5
MAINTENANCE
ORIGINAL INSTRUCTIONS 153
Fault Message Probable cause Action Type
RESET EMERGENCY
A manual reset is required after the
emergency button has been
released or when starting the
Conveyor Control System
Press R to enable the conveyor belt and the
ejector.
Without emergency buttons, leave J5 4-5
jumpered.
EXTERN EMERGENCY
The external emergency button has
been pressed (J13 3-4 open)
After the emergency button has been released,
Emergency reset is required (see above).
Without emergency buttons, leave J13 3-4
jumpered.
-
EMERG.CIRC.FAULT
Emergency circuit faulty.
((J13 5-6 or 9-10 open)
Check the Emergency button connections. After
removing the cause, press the Emergency Reset
button to reset the Fault status. If the problem
persists, contact Assistance Service.
-
BIN FULL
Reject bin full Empty the bin.
Sensor connected to the BIN FULL
input faulty or disconnected
Check the sensor mechanical and electrical
installation.
Check the correct programming, simulating the
input activation and verify (in I/O Status menu) that
the status changes correctly.
If the problem persists, contact Assistance
Service.
BIN ABSENT
Reject bin absent or not correctly in
position
Put the bin back in the correct position.
Sensor connected to the BIN
ABSENT input faulty or
disconnected
Check the sensor mechanical and electrical
installation.
Check the correct programming, simulating the
input activation and verify (in I/O Status menu) that
the status changes correctly.
If the problem persists, contact Assistance
Service.
LOW AIR PRESSURE
Air supply pressure too low Check the air supply connection and pressure.
Sensor connected to the LOW
PRESSURE input faulty or
disconnected
Check the sensor electrical installation.
Check the correct programming, simulating the
input activation and verify (in I/O Status menu) that
the status changes correctly.
If the problem persists, contact Assistance
Service.
NO EJECT.CONFIRM
Product ejection not correctly
confirmed
Check that the ejector is correctly activated and
that the product is properly ejected.
Self-diagnosis not correctly set
Check that the ejection confirmation diagnosis is
correctly programmed for the application.
Sensor connected to the
EJ.CONFIRMATION input faulty or
disconnected
Check the sensor mechanical and electrical
connections. If the problem persists, contact
Assistance Service.
continue >>