User Manual Section 3
GFK-2958L May 2021
Configuration 44
Product
Part No.
Parameter
Optional values
Default value
Analog Input, 4
Channels
Voltage/ Current
16 Bits with
Diagnostics 2-,
3-, or 4-Wire
EP-3264
Frequency suppression
disabled (0) /
50 Hz (1) /
60 Hz (2) /
Average over 16 values (3)
disabled
Ch 0 … Ch 3:
Channel diagnosis
disabled (0) /
enabled (1)
disabled
Ch 0 … Ch 3:
Diag short circuit 24V
disabled (0) /
enabled (1)
disabled
Ch 0 … Ch 3:
Diag line break 24V
disabled (0) /
enabled (1)
disabled
Ch 0 … Ch 3: Measurement
range
0 to 20 mA (0) /
4 to 20 mA (1) /
0 V to 10 V (2) /
-10 to 10 V (3) /
0 to 5 V (4) /
-5 to 5 V (5) /
1 to 5 V (6) /
2 to 10 V (7) /
disabled (8)
disabled
Analog Input,
4 Channels
Voltage/ Current
16 Bits with
Diagnostics
2-, 3-, or 4-Wire,
Differential
EP-3664
Frequency suppression
disabled (0) /
50 Hz (1) /
60 Hz (2) /
Average over 16 values (3)
disabled
Ch 0 … Ch 3:
Channel diagnosis
disabled (0) /
enabled (1)
disabled
Ch 0 … Ch 3:
Diag short circuit 24V
disabled (0) /
enabled (1)
disabled
Ch 0 … Ch 3:
Diag line break 24V
disabled (0) /
enabled (1)
disabled
Ch 0 … Ch 3: Measurement
range
0 to 20 mA (0) /
4 to 20 mA (1) /
0 V to 10 V (2) /
-10 to 10 V (3) /
0 to 5 V (4) /
-5 to 5 V (5) /
1 to 5 V (6) /
2 to 10 V (7) /
disabled (8)
disabled