3.4 Programming Mode
3-24
Table 3.4-8 I/O Check Items
LED
monitor
shows:
Item Unit
Description
4_00
I/O signals on the control circuit
terminals
--
Shows the ON/OFF state of the digital I/O terminals. Refer to
Displaying control I/O signal terminalson the next page
for details.
4_01
I/O signals on the control circuit
terminals under communications
control
--
Shows the ON/OFF state of the digital I/O terminals that
received a command via RS-485 or field bus option. Refer to
Displaying control I/O signal terminalsand
Displaying control I/O signal terminals under
communications controlon the following pages for details.
4_02
Input voltage on terminal [12] V
Shows the input voltage (with sign) on terminal [12] in volts
(V).
4_03
Input current on terminal [C1]
(C1 function)
mA
Shows the input current on terminal [C1] (C1 function) in
milliamperes (mA).
4_04
Output voltage on terminal [FM]
(FMV)
V Shows the output voltage on terminal [FM] (FMV) in volts (V).
4_05
Output voltage on terminal [FM2]
(FMV2)
V
Shows the output voltage on terminal [FM2] (FMV2) in volts
(V). (exclusive to Model: -C/-GB)
4_06
Output frequency on terminal
[FM] (FMP)
p/s
Shows the output pulse rate per unit of time on terminal [FM]
(FMP) in (p/s). (If the value is 10000 or greater, the x10 LED
turns ON and the LED monitor shows one-tenth of the value.)
4_07
Input voltage on terminal [C1]
(V2 function)
V
Shows the input voltage on terminal [C1] (V2 function) in volts
(V).
4_08
Output current on terminal [FM]
(FMI)
mA
Shows the output current on terminal [FM] (FMI) in
milliamperes (mA).
4_09
Output current on terminal [FM2]
(FMI2)
mA
Shows the output current on terminal [FM2] (FMI2) in
milliamperes (mA). (exclusive to Model: -C/-GB)
4_10
Option control circuit terminal
(I/O)
--
Shows the ON/OFF state of the digital I/O terminals on the
digital input and output interface cards (DIO options). Refer to
Displaying
control I/O signal terminals on optional digital
input and output interface cardson page3-26 for details.
4_11
Terminal [X5] pulse input monitor -- Shows the pulse rate of the pulse train signal on terminal [X5].
4_15
PG pulse rate
(A/B phase signal from the
reference PG)
p/s
Shows the pulse rate (p/s) of the A/B phase signal fed back
from the reference PG.
4_16
PG pulse rate
(Z phase signal from the
reference PG)
p/s
Shows the pulse rate (p/s) of the Z phase signal fed back from
the reference PG.
4_17
PG pulse rate
(A/B phase signal from the slave
PG)
p/s
Shows the pulse rate (p/s) of the A/B phase signal fed back
from the slave PG.
4_18
PG pulse rate
(Z phase signal from the slave
PG)
p/s
Shows the pulse rate (p/s) of the Z phase signal fed back from
the slave PG.
4_20
Input voltage on terminal [32] V
Shows the input voltage on terminal [32] on the analog
interface card (AIO option) in volts (V).
4_21
Input current on terminal [C2] mA
Shows the input current on terminal [C2] on the analog
interface card (AIO option) in milliamperes (mA).
4_22
Output voltage on terminal [AO] V
Shows the output voltage on terminal [AO] on the analog
interface card (AIO option) in volts (V).
4_23
Output current on terminal [CS] mA
Shows the output current on terminal [CS] on the analog
interface card (AIO option) in milliamperes (mA).
4_24
Customizable logic timer monitor --
Monitors the timer or counter value in the customizable logic
specified by U91.

Table of Contents

Related product manuals