EasyManua.ls Logo

Fuji Electric FRENIC-Ace series - Page 119

Fuji Electric FRENIC-Ace series
788 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.4 Programming Mode
3-25
OPERATION USING THE KEYPAD
Chap 3
Displaying control I/O signal terminals
The status of control I/O signal terminals can be displayed in two ways: with ON/OFF of each LED segment and in
hexadecimal.
Displaying the I/O signal status with ON/OFF of each LED segment
As shown in Table 3.4-9 and the figure below, each of segments “a” to dpon LED1 and LED2 lights when the
corresponding digital input terminal circuit ([FWD], [REV], [X1] to [X5], [EN1] and [EN2]) is closed (ON); it goes OFF
when it is open (OFF). Segment “a” or “b” on LED3 lights when the circuit between output terminal [Y1] or [Y2] and
terminal [CMY] is closed, respectively; it goes OFF when the circuit is open. Segment “a” on LED4 is for terminals
[30A/B/C] and lights when the circuit between terminals [30C] and [30A] is short-circuited (ON) and goes OFF when
it is open.
If all terminal signals are OFF (open), segments “g” on all of LED1 to LED4 will light (“– – – –”).
Table 3.4-9 Display of I/O Signal Status with ON/OFF of each LED segment
Segment LED4 LED3 LED2 LED1
a 30A/B/C Y1-CMY FWD
b Y2-CMY REV
c X1
d EN1 X2
e EN2 X3
f (XF) * X4
g (XR) * X5
dp (RST) *
: No corresponding control circuit terminal exists
* (XF), (XR), and (RST) are assigned for communications control. Refer to Displaying control I/O signal
terminals under communications controlon page 3-26.
Displaying I/O signal status in hexadecimal
Each I/O terminal is assigned to bit 15 through bit 0 as shown in Table 3.4-10. An unassigned bit is interpreted as
0.Allocated bit data is displayed on the LED monitor as four hexadecimal digits (
0
to
f
each).
On the FRENIC-Ace, digital input terminals [FWD] and [REV] are assigned to bits 0 and 1, respectively. Terminals
[X1] through [X5] are assigned to bits 2 through 6. The bit is set to “1” when the corresponding input terminal is
short-circuited (ON), and it is set to “0” when the terminal is open (OFF). For example, when [FWD] and [X1] are ON
(short-circuited) and all the others are OFF (open),
0005
is displayed on LED4 to LED1.
Digital output terminals [Y1] and [Y2] are assigned to bits 0 through 3. Each bit is set to “1” when the output terminal
[Y1] or [Y2] is short-circuited with [CMY] (ON), and “0” when it is open (OFF).
The status of the relay contact output terminals [30A/B/C] is assigned to bit 8. It is set to “1when the circuit between
output terminals [30A] and [30C] is closed, and “0” when the circuit between [30A] and [30C] is open.
For example, if [Y1] is ON, [Y2] is OFF, and the circuit between [30A] and [30C] is closed, then
0101
is displayed
on the LED4 through LED1.
Table 3.4-10 presents bit assignment and an example of corresponding hexadecimal display on the 7-segment
LED.

Table of Contents

Related product manuals