5.2 Function Codes Table
5-19
FUNCTION CODES
Chap 5
Code Name Data setting range
Change when running
Data copying
Factory
Default
Drive control
Related page
V/f
PG V/f
w/ PG
Torque control
PM
H78
Maintenance interval (M1)
0 (Disable): 1 to 9999 (in units of ten hours)
Y
N
6132
(ND spec)
Y
Y
Y
Y
Y
5-177
H79
Preset startup count for
maintenance (M1)
0000 (Disable): 0001 to FFFF (in hexadecimal)
Y
N
0
Y
Y
Y
Y
Y
5-178
H80
Output current fluctuation
damping gain for motor 1
0.00 to 1.00
Y
Y
0.20
Y
Y
N
N
N
5-178
H81
Light alarm selection 1
0000 to FFFF (in hexadecimal)
Y
Y
0
Y
Y
Y
Y
Y
5-179
H82
Light alarm selection 2
0000 to FFFF (in hexadecimal)
Y
Y
0
Y
Y
Y
Y
Y
H84
Pre-excitation *5 (Level)
100 to 400 % (Motor rated magnetizing current for 100%)
Y
Y
100
N
N
Y
Y
N
5-181
H85
(Timer)
0.00; 0.01 to 30.00 s
0.00; Invalid
0.01 to 30.00 s
Y
Y
0.00
N
N
Y
Y
N
H86
Reserved *9
0 to 2
Y
Y
0
5-183
H89
Reserved *9
0 to 1
Y
Y
1
5-183
H90
Reserved *9
0 to 1
Y
Y
0
5-183
H91
PID feedback wire break
detection
0.0 (Alarm disable): 0.1 to 60.0 s
Y
Y
0.0
Y
Y
Y
N
Y
5-183
H92
Continuous running at the
momentary power failure (P)
0.000 to 10.000 times; 999
999:Manufacturer adjustment value
Y
Y1
Y2
999
Y
Y
Y
N
Y
5-183
H93
(I)
0.010 to 10.000 s; 999
999:Manufacturer adjustment value
Y
Y1
Y2
999
Y
Y
Y
N
Y
H94
Cumulative motor run time 1
0 to 9999
Change in cumulative motor run time (Reset is enabled)
(in units of 10 hours)
N
N
Y
Y
Y
Y
Y
5-177
5-183
H95
DC braking
(Braking response mode)
0: Slow response
1: Quick response
Y
Y
1
Y
Y
N
N
N
5-74
5-183
H96
STOP key priority/
Start check function
0: STOP key priority disable/ Start check function disable
1: STOP key priority enable/ Start check function disable
2: STOP key priority disable/ Start check function enable
3: STOP key priority enable/ Start check function enable
Y
Y
U:3
ACEJK:0
Y
Y
Y
Y
Y
5-184
H97
Clear alarm data
0: Disable
1: Alarm data clear (Automatically return to 0 after
clearing data)
Y
N
0
Y
Y
Y
Y
Y
5-184
H98
Protection/Maintenance
function (Mode selection)
0 to 127 (Data is displayed in decimal)
Bit 0: Lower the carrier frequency automatically
(0: Disable; 1: Enable)
Bit 1: Input phase loss protection (0: Disable; 1: Enable)
Bit 2: Output phase loss protection (0: Disable; 1: Enable)
Bit 3: Main circuit capacitor life judgment selection
(0: Factory default referenced;
1 User measurement value standard)
Bit 4: Judge the life of main circuit capacitor
(0: Disable; 1: Enable)
Bit 5: Detect DC fan lock (0: Enable; 1: Disable)
Bit 6: Braking transistor error detection
(0: Disable; 1: Enable)
Y
Y
*11
Y
Y
Y
Y
Y
5-185
H99
Password 2 setting/check
0000 to FFFF (Hexadecimal)
Y
N
0
Y
Y
Y
Y
Y
5-187
H101
Destination
0: Not selected
1: Japan
2: Asia
3: China
4: Europe
5: Americas
7: Korea
N
Y
G(AEU):0
J:1
C:3
K:7
Y
Y
Y
Y
Y
5-190
H111
UPS operation level
120 to 220 VDC: (200 V class)
240 to 440 VDC: (400 V class)
Y
Y2
220
440
Y
Y
Y
N
N
5-190
H114
Anti-regenerative control
(Level)
0.0 to 50.0%, 999: disabled
Y
Y
999
Y
Y
Y
N
Y
5-190
H147
Speed control (Jogging)
FF (Gain) *5
0.00 to 99.99 s
Y*
Y
0.00
N
N
Y
N
N
5-190
5-230
Factory default

A (For Asia), C (for China), E (for Europe), U (For USA), J (for Japan), K (for Korea)
*5: Available at ROM version 0300 or later.
*9: Factory use. Do not access these function codes.
*11: FRN0115E2
-2
or below: 83, FRN0072E2
-4
or below: 83, FRN0012E2
-7
or below: 83, FRN0085E2
-4
or above: 19.