5.2 Function Codes Table
5-21
FUNCTION CODES
Chap 5
A codes: Motor 2 Parameters (Motor 2 parameters)
Code
Name Data setting range
Change when running
Data copying
Factory
Default
Drive control
Related page
V/f
PG V/f
w/ PG
Torque control
PM
A01
Maximum output frequency 2
25.0 to 500.0Hz
N
Y
200V class
AJKU:60.0
400V class
ACE:50.0
JKU:60.0
Y
Y
Y
Y
N
A02
Base frequency 2
25.0 to 500.0Hz
N
Y
200V class
J:50.0
AUK:60.0
400V class
ACEJ:50.0
UK:60.0
Y
Y
Y
Y
N
A03
Rated voltage at base
frequency 2
0: AVR disable (output voltage proportional to power
voltage)
80 to 240V: AVR operation ( 200V class)
160 to 500V: AVR operation ( 400V class)
N
Y2
200V class
J:200
AK:220
U:230
400V class
EJ:400
A:415
CK:380
U:460
Y
Y
Y
Y
N
A04
Maximum output voltage 2
80 to 240V: AVR operation ( 200V class)
160 to 500V: AVR operation ( 400V class)
N
Y2
Y
Y
N
Y
N
A05
Torque boost 2
0.0 to 20.0% (% value against base frequency voltage 2)
Y
Y
*2
Y
Y
N
N
N
A06
Electronic thermal overload
protection for motor 2
(Select motor characteristics)
1: Enable (For a general-purpose motor with self-cooling
fan)
2: Enable (For an inverter-driven motor with separately
powered cooling fan)
Y
Y
1
Y
Y
Y
Y
N
A07
(Overload detection level)
0.00 (disable), current value of 1 to 135% of inverter rated
current
Y
Y1
Y2
*3
Y
Y
Y
Y
N
A08
(Thermal time constant)
0.5 to 75.0 min
Y
Y
*4
Y
Y
Y
Y
N
A09
DC braking 2
(Braking starting frequency)
0.0 to 60.0Hz
Y
Y
0.0
Y
Y
Y
N
N
A10
(Braking level)
0 to 100% (HHD mode), 0 to 80% (HD/HND mode)
0 to 60% (ND mode)
Y
Y
0
Y
Y
Y
N
N
A11
(Braking time)
0.00 (Disable): 0.01 to 30.00 s
Y
Y
0.00
Y
Y
Y
N
N
A12
Starting frequency 2
0.0 to 60.0Hz
Y
Y
0.5
Y
Y
Y
N
N
A13
Load selection /
Auto torque boost/
Auto energy-saving
operation 2
0: Variable torque load
1: Constant torque load
2: Auto torque boost
3: Auto energy-saving operation (variable torque load)
4: Auto energy-saving operation (constant torque load)
5: Auto energy-saving operation with auto torque boost
N
Y
1
Y
Y
Y
N
N
A14
Drive control selection 2
0: V/f control without slip compensation
1: Vector control without speed sensor (Dynamic torque
vector control)
2: V/f control with slip compensation
3: V/f control with speed sensor
4: V/f control with speed sensor and auto torque boost
6: Vector control for induction motor with speed sensor
N
Y
0
Y
Y
Y
Y
N
A15
Motor 2 (No. of poles)
2 to 22 poles
N
Y1
Y2
4
Y
Y
Y
Y
N
A16
(Rated capacity)
0.01 to 1000 kW (At P39 = 0, 4)
0.01 to 1000 HP (At P39 = 1)
N
Y1
Y2
*6
Y
Y
Y
Y
N
A17
(Rated current)
0.00 to 2000A
N
Y1
Y2
*6
Y
Y
Y
Y
N
A18
(Auto-tuning)
0: Disable
1: Stop tuning
2: Rotation tuning
5: Stop tuning (%R1, %X)
N
N
0
Y
Y
Y
Y
N
A19
(Online tuning)
0: Invalid 1:Valid
Y
Y
0
Y
N
N
N
N
A20
(No-load current)
0.00 to 2000A
N
Y1
Y2
*6
Y
Y
Y
Y
N
A21
(%R1)
0.00 to 50.00%
Y
Y1
Y2
*6
Y
Y
Y
Y
N
A22
(%X)
0.00 to 50.00%
Y
Y1
Y2
*6
Y
Y
Y
Y
N
Factory default

A (For Asia), C (for China), E (for Europe), U (For USA), J (for Japan), K (for Korea)
*2: Factory defaults are depended on motor capacity. Refer to 5.2.3 Factory default value per applicable electric motor capacitance”.
*3: The motor rated current is automatically set. Refer to 5.2.4 Motor constant(function code P03).
*4: Standard applicable electric motor is 5.0 min for 22 kW or lower and 10.0 min for 30 kW or higher.
*6: Factory defaults are depended on motor capacity. Refer to 5.2.4 Motor constant”.