5.2 Function Codes Table
5-21
FUNCTION CODES
Chap 5
■ A codes: Motor 2 Parameters (Motor 2 parameters)
Code
Name Data setting range
Change when running
Data copying
Factory
Default
Maximum output frequency 2
J:50.0
AUK:60.0
400V class
0: AVR disable (output voltage proportional to power
voltage)
80 to 240V: AVR operation ( 200V class)
160 to 500V: AVR operation ( 400V class)
J:200
AK:220
U:230
400V class
80 to 240V: AVR operation ( 200V class)
160 to 500V: AVR operation ( 400V class)
0.0 to 20.0% (% value against base frequency voltage 2)
Electronic thermal overload
(Select motor characteristics)
1: Enable (For a general-purpose motor with self-cooling
fan)
2: Enable (For an inverter-driven motor with separately
(Overload detection level)
0.00 (disable), current value of 1 to 135% of inverter rated
current
DC braking 2
(Braking starting frequency)
0 to 100% (HHD mode), 0 to 80% (HD/HND mode)
0 to 60% (ND mode)
0.00 (Disable): 0.01 to 30.00 s
Auto torque boost/
Auto energy-saving
operation 2
1: Constant torque load
2: Auto torque boost
3: Auto energy-saving operation (variable torque load)
4: Auto energy-saving operation (constant torque load)
5: Auto energy-saving operation with auto torque boost
Drive control selection 2
0: V/f control without slip compensation
1: Vector control without speed sensor (Dynamic torque
vector control)
2: V/f control with slip compensation
3: V/f control with speed sensor
4: V/f control with speed sensor and auto torque boost
6: Vector control for induction motor with speed sensor
0.01 to 1000 kW (At P39 = 0, 4)
0.01 to 1000 HP (At P39 = 1)
1: Stop tuning
2: Rotation tuning
Factory default
A (For Asia), C (for China), E (for Europe), U (For USA), J (for Japan), K (for Korea)
*2: Factory defaults are depended on motor capacity. Refer to “5.2.3 Factory default value per applicable electric motor capacitance”.
*3: The motor rated current is automatically set. Refer to “5.2.4 Motor constant” (function code P03).
*4: Standard applicable electric motor is 5.0 min for 22 kW or lower and 10.0 min for 30 kW or higher.
*6: Factory defaults are depended on motor capacity. Refer to “5.2.4 Motor constant”.